A.7.11ISO 27001:2022 Annex A

Supporting utilities

ISO/IEC 27002:2022 attributes

Control type
Preventive · Detective
Security properties
Integrity · Availability
Cybersecurity concept
Protect · Detect
Operational capability
Physical security
Security domain
Protection

Attribute tags as published in ISO/IEC 27002:2022, compiled from public listings — confirm against your licensed copy.

Plain-language summary

Protecting information processing facilities against failures and disruptions in the utilities they depend on — electricity, telecommunications, water, cooling and ventilation — through backup supply, monitoring and testing sized to how long you must keep running.

What the clause is really asking

Equipment is useless without power, cooling and connectivity, and this control asks you to make sure a failure in those utilities does not take your information processing down with it. That means knowing which utilities each critical facility relies on, checking they meet specifications and have capacity for growth, testing them regularly, alarming on failure, and providing alternative feeds or backup where justified. In South Africa this is a live availability threat: load-shedding, municipal supply failures, cable theft and voltage spikes when power is restored. The design questions are concrete: how long does the UPS hold the servers, does the generator start automatically and how much fuel is on site, are firewalls, fibre terminals, routers and access control on backup too, and what happens when the provider's exchange or cell tower runs out of battery. The misunderstanding is that a UPS is enough; batteries age, untested generators fail to start, and cooling often goes down while the servers stay up. Your plant maintenance system already tracks the generator; add the IT dependencies.

What auditors look for

Auditors ask for the list of utilities supporting critical facilities and the backup for each. They check UPS runtime against the outage you plan for, battery age and test records, and generator start tests under load, fuel level and refuelling arrangements. They ask whether cooling, network equipment and the alarm system are on backup power. They look for alerts on power state, UPS status and temperature. They ask about the second internet link and whether it takes a different route. The hard question: when did you last switch off the mains and run on backup, and what failed?

Typical evidence

Utility dependency list for critical facilities; UPS specifications, runtime calculations and battery test or replacement records; generator service and load test records; fuel management and refuelling arrangements; power and environmental monitoring alerts; redundant internet or telecom links with diverse routing; cooling maintenance records; outage records showing how systems performed.

How to comply — recommendations

List what each critical facility needs: power, cooling, network and, where relevant, water. Work out the runtime you need from your longest likely outage and size UPS, inverter and generator capacity to match, including firewalls, switches, fibre terminals, access control and CCTV. Test the generator monthly under load and run a full mains-off test at least twice a year. Replace UPS batteries on a schedule. Add a second internet link from a different provider or medium. Set alerts for power state and server room temperature. Put this equipment into the plant maintenance system so it gets the same discipline as production assets.

Common nonconformities

UPS batteries expired or never tested; generator not load-tested, or no fuel plan; network, cooling or alarm systems not on backup power; single internet link with no alternative; no monitoring or alerting on power and cooling; backup runtime not matched to expected outage length; outages cause unplanned shutdowns and data corruption.

Related clauses

ISO/IEC 27002:2022 7.11 (guidance); ISO 27001 6.1.2, 8.1; Annex A 5.29–5.30 (continuity), 7.5, 7.8, 7.12, 7.13, 8.14 (redundancy); NIST CSF 2.0 PR.IR (technology infrastructure resilience); ISO 9001 7.1.3 (infrastructure); ISO 22301 (business continuity).

Resources for this clause

Get the free ISO 27001 Annex A — 93 Controls Quick Reference (A3 PDF)

Free, instant download. We'll only email you the occasional practical quality update — no spam, unsubscribe anytime.

Qlause provides interpretive guidance only and is not a substitute for the standard. Refer to your licensed copy of the relevant standard for the authoritative text.

Certification & implementation

Working on a certification or system implementation project?

Implementing ISO 9001, moving to the 2026 edition, getting ready for a certification audit, or stuck on a clause that doesn't seem to fit your operation? Tell us where you are and where you're stuck. We'll look at it and suggest a practical next step, or connect you with people we trust who can help.